CAN/ULC 646:2024
Scope
1.1 These requirements cover Type I commercial kitchen exhaust hoods intended for placement over
commercial cooking equipment. Exhaust hoods with and without exhaust dampers are covered by these
requirements.
1.2 Exhaust hoods with and without exhaust fire actuated fire dampers are covered by these
requirements.
1.3 Exhaust hoods are evaluated relative to minimum exhaust air flow required and maximum supply air
flow allowed for capture and containment of cooking effluents under laboratory conditions.
1.4 Exhaust hoods may incorporate non-continuous welded joints, seams, and penetrations when
evaluated by these requirements.
1.5 Exhaust hoods with fire actuated fire exhaust dampers are intended to have the exhaust fire actuated
dampers automatically close to prevent exhaust duct gas temperatures from exceeding 191 °C (375 °F).
1.6 These requirements do not cover fire-extinguishing systems.
NOTE: All exhaust hoods are intended for use with fire extinguishing system units.
1.7 These requirements cover exhaust hoods provided with manually or automatically operated cleaning
or washing systems. These requirements do not cover the fire extinguishing aspects of such systems.
1.8 These requirements do not cover evaluation of Ultraviolet (UV) systems for use in commercial
kitchen exhaust systems. Annex A covers the requirements of these products.
1.9 These requirements do not cover evaluation of Electrostatic Precipitators (ESP's) for use in
commercial kitchen ventilation. Electrostatic Precipitators (ESP's) are covered under the Standard for
Electrostatic Air Cleaners, UL 867.
1.10 These requirements do not cover evaluation of commercial electric cooking appliances provided
with integral recirculating systems (previously referred to as ductless hoods) and nonintegral recirculating
systems, both of which are intended for installation in commercial establishments for the preparation of
food. The Standard for Recirculating Systems, UL 710B, covers these products.
1.11 Exhaust hoods covered by these requirements are intended for installation in accordance with the
following:
a) The Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations,
NFPA 96;
b) The National Electrical Code, NFPA 70, in the United States, and Canadian Electrical Code, Part
I, CSA C22.1, in Canada; and/or
c) Other codes such as the International Mechanical Code (IMC), National Building Code of
Canada (NBC), and the Uniform Mechanical Code (UMC).
1.12 These requirements cover products rated 600 volts or less.
1.13 These requirements do not cover evaluation of the exhaust hoods with respect to their grease
extraction efficiency.
NOTE: Capture efficiency of a kitchen hood filter can be measured using ASTM F2519, Standard Test Method for Grease Particle
Capture Efficiency of Commercial Kitchen Filters and Extractors.