ANSI/CAN/UL/ULC 25B:2024
Scope
1.1 These requirements cover positive displacement liquid meters for use with motor fuels. Motor fuels,
as defined by these requirements, include one or more of the fuels described in 1.3.
1.2 Meters for Diesel Fuel, Biodiesel Fuel, Diesel/Biodiesel Blends with Nominal Biodiesel
Concentrations up to 20 Percent (B20), Kerosene, and Fuel Oil shall be constructed to comply with the
following:
a) The requirements defined in the Standard for Meters for Flammable and Combustible Liquids
and LP-Gas, UL/ULC 25; and
b) The requirements in this Standard.
1.3 Meters covered by these requirements are intended for use with one or more of the following as
applicable:
a) Diesel fuel, which includes renewable diesel and diesel/biodiesel blends with nominal biodiesel
concentrations up to 5 % (B0-B5) formulated in accordance with the Standard Specification for
Diesel Fuel Oils, ASTM D975;
b) Diesel/biodiesel, renewable diesel/biodiesel blends, blends with nominal biodiesel
concentrations from 5 % up to 20 % (B6 – B20) formulated in accordance with the Standard
Specification for Diesel Fuel Oil, Biodiesel Blends (B6 – B20), ASTM D7467;
c) Biodiesel (B99.9/B100) formulated in accordance with the Standard Specification for Biodiesel
Fuel Blend Stock (B100) for Middle Distillate Fuels, ASTM D6751;
d) Kerosene formulated in accordance with the Standard Specification for Kerosine, ASTM D3699;
or
e) Fuel oil (heating oil) formulated in accordance with the Standard Specification for Fuel Oils,
ASTM D396.
1.4 Products covered by this Standard are intended to be installed and used in accordance with the
applicable Codes and Regulations as determined by the Authority Having Jurisdiction (AHJ), such as, but
not limited to:
a) In the United States:
1) Flammable and Combustible Liquids Code, NFPA 30;
2) Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A;
b) In Canada:
1) The National Fire Code of Canada;
2) Provincial or other Regulations.
1.5 These requirements do not cover:
a) Meters for use with fuels other than as described in 1.3;
b) Velocity meters, head meters, or area meters;
c) Meters for use in centralized fuel oil distribution systems; and
d) Meter components incorporating electrical circuits except those meeting intrinsically safe or
explosion standards.
1.6 Determinations of the suitability of registers, counters, or computers used or provided with these
meters, or the accuracy of measurement resulting from or required in actual application are not within the
scope of these requirements.
1.7 For requirements for meters for gasoline/ethanol blends with nominal ethanol concentrations above
10 %, refer to the Standard for Meters for Gasoline and Gasoline/Ethanol Blends with Nominal Ethanol
Concentrations up to 85 Percent (E0 – E85), UL/ULC 25A, for additional requirements.
OEN:
ULC
Langue:
English
Code(s) de l'ICS:
17.120.01;
75.160.20;
75.180.30
Statut:
Norme
Date de Publication:
2024-05-30
Numéro Standard:
ANSI/CAN/UL/ULC 25B:2024