CSA C22.2 No. 268:22
1 Scope
1.1 These requirements apply to low-voltage AC power circuit breakers as follows:
a) Stationary-mounted or drawout-mounted types,
b) 2-pole, 3-pole, and 4-pole constructions,
c) Manually operated or power operated, and
d) With or without electromechanical or solid-state type trip device.
1.2 These requirements apply to drawout-mounted type low-voltage AC integrally fused power circuit
breakers, consisting of low-voltage AC power circuit breakers with integral fuses.
1.3 These requirements apply to low-voltage AC fuse draw-outs consisting of fuses in a drawout
assembly intended to be connected in series with a low-voltage AC power circuit breaker to form a fused
circuit breaker.
1.4 These requirements apply to general purpose type DC power circuit breakers.
1.5 These requirements apply to equipment rated 1000 V or less nominal, 1058 V maximum AC and
1500 V maximum DC.
1.6 These requirements apply to equipment intended for use in ordinary locations in accordance with
Annex A, Ref. No. 1.
1.7 These requirements are intended to supplement and be used in conjunction with the:
a) Standard for Low-Voltage AC Power Circuit Breakers Used In Enclosures, IEEE C37.13 (see
Annex A, Ref. No. 7),
b) Standard for DC (3200 V and below) Power Circuit Breakers Used in Enclosures, IEEE C37.14
(see Annex A, Ref. No. 8),
c) Standard for Metal-Enclosed Low-Voltage (1000 Vac and below, 3200 Vdc and below) Power
Circuit Breaker Switchgear, IEEE C37.20.1 (see Annex A, Ref. No. 9),
d) Test Procedures for Switchgear – Low-Voltage AC Power Circuit Breakers Used In Enclosures,
ANSI C37.50 (see Annex A, Ref. No. 10), and
e) Conformance Test Procedures for Switchgear – Metal-Enclosed Low-Voltage AC Power Circuit
Breaker Switchgear Assemblies, ANSI C37.51 (see Annex A, Ref. No. 11).
1.8 This Standard does not apply to molded-case circuit breakers.
1.9 These circuit breakers are intended for installation in circuit breaker enclosures, switchboards
(switchgear), panelboards, and the like. Drawout-mounted devices are intended for use with specific
adapters or receiving equipment. The acceptability of the combination of a circuit breaker with respect to
any overall enclosure will be determined when the complete product is considered.
OEN:
CSA
Langue:
English
Code(s) de l'ICS:
N/A
Statut:
Norme
Date de Publication:
2022-07-31
Numéro Standard: