CAN/ULC-S127-14-R2019
1 SCOPE
1.1 This method of test for flammability characteristics is applicable to certain low density insulating
materials that do not melt or drip during exposure to fire (see Appendix A). It is used in establishing the
Flame Spread Classification for those foamed plastics whose flammability assessment found in
CAN/ULC-S102, Standard Method of Test for Surface Burning Characteristics of Building Materials and
Assemblies, requires the use of the rate formula FSV = 92.5 d/t but where the necessary parameters (’d’
& ’t’) for use in the formula are difficult to define.
Note : In the formula FSV = 92.5 d/t, ’t’ is the time in minutes for the flame front to propagate a distance of ’d’ metres
where there is a marked reduction in the advance of the flame front during the test in CAN/ULC-S102, Standard
Method of Test for Surface Burning Characteristics of Building Materials and Assemblies.
1.2 The purpose of this test is to determine the comparative burning characteristics of the material under
test by exposing the material in a corner wall configuration to a test fire.
1.3 It is the intent of this method to register performance during the period of exposure and not to
determine suitability for use after the test exposure.
OEN:
ULC
Langue:
English
Code(s) de l'ICS:
13.220.50;
19.040;
91.060.10
Statut:
Norme
Date de Publication:
2014-09-30
Numéro Standard:
CAN/ULC-S127-14-R2019