CAN/CSA-C50089-99 (R2016)
2 Scope
2.1 Type of equipment
This Standard applies to cast resin partitions pressurized with inert gases,
eg, sulphur hexafluoride, carbon tetrafluoride, or a mixture of such gases,
such as sulphur hexafluoride and nitrogen used in indoor or outdoor
installations of high-voltage switchgear and controlgear, where the gas is used
principally for its dielectric and/or arc-quenching properties, with rated
voltages
(a) 1 kV and up to and including 52 kV and with gas-filled compartments with
design pressure greater than 3 bar (gauge); and
(b) 72.5 kV and above.
The partitions comprise pressurized barriers in electrical equipment not
necessarily limited to the following examples:
circuit breakers,
switch disconnectors,
disconnectors,
earthing switches,
current transformers,
voltage transformers,
surge arrestors,
busbars and connections,
cable connections.
This standard does not apply to high-voltage bushings (see HD 358 S3 (IEc
517)).
2.2 Quality assurance
It is the intention of this standard that the switchgear manufacturer shall be
responsible for achieving and maintaining a consistent and adequate quality of
product.
Sufficient examinations shall be made by the partition manufacturer to ensure
that the materials, production and testing comply in all respects with the
requirements of this standard. Inspection by the users' inspectors shall not
absolve the switchgear manufacturer from his responsibility to exercise such
quality assurance procedures as to ensure that the requirements and intent of
this standard are satisfied.
NOTE. The manufacturer should have a quality assurance program registered to
the applicable ISO 9000 series standards.