CSA 2.32-M98
1.1 SCOPE
1.1.1 This standard applies to newly produced vented gas-fired space heating
appliances (see Part XIV, Definitions), hereinafter referred to as
appliance(s), constructed entirely of new, unused parts and materials:
a. For use with natural gas;
b. For use with manufactured gas;
c. For use with mixed gas;
d. For use with liquefied petroleum gases (propane) (also see
2.2-e); and
e. For use with LP gas-air mixtures.
The construction of vented gas-fired space heating appliances for use
with the above-mentioned gases is covered under Part I.
The performance of vented gas-fired space heating appliances for use
with the above-mentioned gases is covered under Part II.
1.1.2 This standard applies only to the following appliance types, as defined
in Part XIV, Definitions:
a. Gravity vented wall furnace;
b. Fan type vented wall furnace;
c. Fan type vented wall furnace with cooling unit;
d. Vented room heater;
e. Gravity direct vent wall furnace;
f. Fan-type direct vent wall furnace; and
g. Floor furnace.
1.1.3 An appliance having a decorative flame which simulates a solid fuel
fire, such as coal or wood, must also comply with the applicable
construction provisions of the Standard for Vented Gas Fireplaces, ANSi
Z21.50 ·CGA 2.22. (See sections, 1.2.17, 1.2.18, 1.2.19, 1.4 (Glass
Fronts), 1.19.7, 1.19.8, 1.26.2-g, 1.26.3, 1.26.4, and 1.27.2-n.)
1.1.4 This standard covers the thermal efficiency and related markings of
only those appliances whose efficiencies are not regulated in the
U.S.A. by the Energy Policy and Conservation Act of 1975 and the
National Energy Conservation Policy Act of 1978* or covered in Canada
by Exhibit B, Items Unique to Canada.
1.1.5 If a value for measurement as given in this standard is followed by an
equivalent value in other units, the first stated value is to be
regarded as the specification.
1.1.6 All references to psi throughout this standard are to be considered
gage pressures unless otherwise specified.
1.1.7 All vented gas-fired space heating appliances shall conform with the
applicable requirements under Part I and Part II. In addition, for
requirements specific to product type also see:
a. Vented Room Heaters - Construction, Part IIi
Vented Room Heaters - Performance, Part IV;
b. Direct Vent Wall Furnaces - Construction, Part v
Direct Vent Wall Furnaces - Performance, Part VI;
c. Gravity and Fan Type Wall Furnaces - Construction, Part VIi
Gravity and Fan Type Wall Furnaces - Performance, Part VIII;
and
d. Floor Furnaces - Construction, Part Ix
Floor Furnaces - Performance, Part X.
1.1.8 Exhibit A, Items Unique to the United States, contains provisions that
are unique to the United States.
1.1.9 Exhibit B, Items Unique to Canada, contains provisions that are unique
to Canada.
1.1.10 Special construction provisions applicable to vented space heating
appliances designed for use with an optional design-certified
conversion kit are outlined under Exhibit J, (Optional) Provisions for
Listed Gas Appliance Conversion Kits.
1.1.11 Exhibit K, List of Reference Standards, contains a list of standards
specifically referenced in this standard, and sources from which these
reference standards may be obtained.
* At the time of this printing, the above acts regulate the thermal efficiency
(heating capacity) of vented appliances. For information, contact the U.S.
Department of Energy, Conservation and Solar Applications, Consumer Products
Efficiency Branch, 20 Massachusetts Avenue, N.W., Washington, DC 20545.