CAN/CSA-C2-M91 (R2003)
1.1
This Standard specifies the requirements for distribution transformers intended
primarily for operation by electric utilities.
Note: The operation of transformers complying with this Standard, by other
than an electric utility, may be subject to additional requirements by the
electrical inspection authority having jurisdiction under Part I of the
Canadian Electrical Code.
1.2
This Standard applies to single- and three-phase, 60 Hz, liquid-filled,
distribution transformers, Types ONAN and LNAN, rated at 1000 kV·A or below for
single-phase and at or below 3000 kV·A for three-phase, insulation class 34.5
kV and less.
1.3
This Standard includes voltage ratings, kV·A ratings, certain mechanical
characteristics, and test procedures. Also included are the following
performance characteristics: temperature rise, loading capabilities, sound
level, and radio influence voltage (RIV).
1.4
This Standard also applies to self-protected transformers, except for the
protective equipment.
1.5
Except as specified by other CSA Standards this Standard does not apply to
auto-, testing, dry-type, welding, furnace, rectifier, network, pad-mounted,
subway-type, or special-purpose transformers, or to step-voltage regulators.
1.6
Transformers built in accordance with this Standard shall meet the quality
requirements of CSA Standard CAN3-Z299.3.
OEN:
CSA
Langue:
English
Code(s) de l'ICS:
29.180
Statut:
Annulée
Date de Publication:
1991-10-30
Numéro Standard:
CAN/CSA-C2-M91 (R2003)