ASSE/IAPMO/ANSI/CAN 1379-2024
Scope
1.2.1 Description
This device consists of a single potable cold water supply inlet and outlet, and a single hydronic
supply inlet and outlet, a means of dynamic flow control, an atmospheric vent, and two sets of
three dynamic seals between the potable and hydronic flow paths.
1.2.2 Threaded or other connections
Pipe threads and other connections shall conform to local plumbing and mechanical codes.
Pipe threads shall comply with ANSI/ASME B1.20.1.
Dryseal threads shall comply with ANSI/ASME B1.20.3.
Female pipe threaded connections shall be so constructed that it is impossible to run a pipe into
them far enough to restrict the flow through the device or interfere with working parts.
Connections achieved by push-fit fittings shall comply with ANSI/ASSE 1061.
Connections achieved by press connect fittings shall comply with ASME B16.51 or
IAPMO/ANSI/CAN Z1117.
Connections achieved by PEX fittings shall comply with ASTM F1807 or F1960.
Other Connections not specified above shall be in accordance with the applicable connection
standard.
1.2.3 Size Range
Inlet and outlet sizes are 19 mm DN 10 (3/4").
1.2.4 Flow Range
The maximum rated flow rate on the potable flow path shall be 0.57 L/sec (9.0 GPM).
The maximum rated flow rate on the hydronic flow path shall be 0.57 L/sec (9.0 GPM).
1.2.5 Temperature Range
The maximum operating temperature for the device is 90°C (195°F).
1.2.6 Pressure Range
The maximum static pressure, on the potable and hydronic flow paths, is 1241 kPa (180 psi.)
OEN:
IAPMO
Langue:
English
Code(s) de l'ICS:
23.060.99;
91.140.60
Statut:
Norme
Date de Publication:
2024-03-31
Numéro Standard:
ASSE/IAPMO/ANSI/CAN 1379-2024