CSA E60730-2-15:24
Scope
This part of IEC 60730 applies to automatic electrical air flow, water flow and water level
sensing controls for use in, or in association with, boilers with a maximum pressure rating of
2 000 kPA (20 bar) and equipment for general household and similar use including controls
for heating, air-conditioning and similar applications.
NOTE Examples are water flow and water level sensing controls of the float or electrode-sensor type used in
boiler applications and air flow, water flow and water level sensing controls for swimming pool pumps, water tank
pumps, cooling towers, dishwashers, washing machines, air conditioning chillers and ventilation applications.
This document also applies to automatic electrical air flow, water flow and water level sensing
controls for equipment that may be used by the public, such as equipment intended to be
used in shops, offices, hospitals, farms and commercial and industrial applications.
1.1.1
Replacement:
This document applies to the inherent safety, to the operating values, operating sequences
where such are associated with equipment protection, and to the testing of automatic
electrical air flow, water flow and water level sensing controls used in, or in association with,
equipment. This Standard applies to equipment that is intended to be installed or used in accordance with
CSA C22.1, Canadian Electrical Code, Part I.
CSA E60730-1. This Standard is also applicable to controls for appliances within the scope of CSA C22.2
No. 60335-1.
This document is also applicable to individual controls utilized as part of a control system or
controls which are mechanically integral with multifunctional controls having non-electrical
outputs.
This document is not applicable to pressure sensing controls, requirements for which are
contained in IEC 60730-2-61.
This document applies to air flow, water flow, and water level sensing controls designed for commercial
and industrial applications unless the relevant equipment Standard does not exist.
NOTE Throughout this document, the word "equipment" means "appliance and equipment".
1.1.2 Addition:
This document applies to automatic electrical controls, mechanically or electrically operated,
responsive to or controlling air flow, water flow and water level.
1.1.3 Not applicable.
NOTE Requirements for manual switches not forming part of an automatic control are contained in IEC 60669 and
IEC 61058-1.
1.1.5 Replacement:
This document applies to a.c. or d.c. automatic electrical air flow, water flow and water level
sensing controls with a rated voltage not exceeding 690 V a.c. or 600 V d.c.
1.1.6 Replacement:
This document takes into account the response value of an automatic action of a control
where such a response value is dependent upon the method of mounting the control. Where a
response value is of significant purpose for the protection of the user, or surroundings, the
value defined in the appropriate household equipment standard or as determined by the
manufacturer shall apply.
1.1.7 Replacement:
This document applies also to controls incorporating electronic devices, requirements for
which are contained in Annex H.
This document applies also to controls using NTC and PTC thermistors, requirements for
which are contained in Annex J.
OEN:
CSA
Langue:
English
Code(s) de l'ICS:
97.120
Statut:
Norme
Date de Publication:
2024-09-30
Numéro Standard:
CSA E60730-2-15:24