ANSI Z21.80-2011/CSA 6.22-2011
1.1 Scope
1.1.1
This standard applies to line pressure regulators, (see Part V, Definitions), constructed entirely of new,
unused parts and materials, hereinafter referred to as regulator(s), either individual or in combination with
over pressure protection devices, hereinafter referred to as device(s), intended for application in gas piping
systems between the service regulator, or LP-gas 2 psi service regulator, and the gas utilization equipment.
1.1.2
This standard applies to regulators for operation with natural, manufactured and mixed gases, liquefied
petroleum gases, and LP gas-air mixtures.
1.1.3
This standard applies to regulators classified in accordance with their intended application with reference
to inlet and outlet pressures as follows.
1.1.4
This standard applies to regulators and devices intended for use in one or more of the following mounting
classifications (also see 1.12-a):
Upright—single position on a horizontal axis with respect to the inlet connection, as specified by the
manufacturer.
Horizontal—any position on a horizontal axis with respect to the inlet connection.
Vertical—any position on a vertical axis with respect to the inlet connection.
Limited Horizontal—any position from upright to 90 degrees (1.57 rad) from upright on a horizontal axis
with respect to the inlet connection.
Multipoise—any position on a horizontal, vertical or intermediate axis with respect to the inlet connection.
The tests specified herein shall be conducted with the regulator mounted in the manufacturer’s specified
upright position, unless otherwise specified herein.
If the manufacturer specifies more than one mounting position, the tests under 2.7, Outlet Pressure
Range, shall be conducted in each mounting position. The data from these tests shall then be analyzed to
determine the mounting position which produces the minimum outlet pressure and the mounting
position which produces the maximum outlet pressure, based on results observed for the minimum outlet
pressure setting of the regulator.
a. The tests under 2.8, Range of Regulation Capacity, shall be conducted in the mounting position
which produces the minimum outlet pressure, as determined in 2.7, Outlet Pressure Range.
b. The tests under 2.8 , Range of Regulation Capacity, and 2.9, Regulator Lockup Pressure, shall also be
conducted in the mounting position that produces the maximum outlet pressure, as determined in
2.7, Outlet Pressure Range.
1.1.5
The tests specified herein shall be conducted at a room temperature of 77 ± 10°F (25 ± 5.5°C). Regulators
and vent limiters complying with the provisions of this standard shall be considered as having an
operating temperature range of 32°F (0°C) to 125°F (51.5°C). At the option of the manufacturer, a greater
operating temperature range may be specified, in which case additional tests as outlined in 2.4, Leakage,
and 2.10, Continued Operation, shall be conducted.
1.1.6
If a value for measurement as given in this standard is followed by an equivalent value in other units, the
first stated value is to be regarded as the specification.
1.1.7
All references to psi throughout this standard are to be considered gauge pressures unless otherwise
specified.