CAN/ULC-S115-05
1. SCOPE
1.1 This method of test is applicable to firestop systems with or without penetrating
items. These firestop systems are intended for use in openings in fire resistive wall and floor
assemblies and membranes forming part of an assembly required to have a fire resistance
rating and linear openings between adjacent fire resistive floor assemblies, wall assemblies or
both.1.2 Tests conducted in conformance with this method will record firestop
performance during the fire-test exposure under laboratory conditions; but such tests shall not
be construed as determining suitability of the firestop system for use after exposure to fire.
1.3 The test method allows for the testing of the resistance of firestop systems to an
external force simulated by a hose stream. However, this method shall not be construed as
determining the performance of the firestop during actual fire conditions when subjected to
forces such as failure of cable support systems and falling debris.
1.4 Provisions are included to allow for testing with a pressure differential between
the furnace chamber and the exterior.
1.5 It is the intent that tests made in conformity with these test methods will develop
data to enable regulatory bodies to determine the suitability of firestop systems for use in
assemblies where fire resistance of a specified duration is required.
1.6 Provisions are included to allow for optional air leakage testing to determine the
air leakage rate through test specimens resulting from a specified air pressure difference
applied across the surface of the test specimens. The results of this test are intended to develop
data to assist in determining the acceptability of firestop systems with reference to the control of
air movement.
NOTE: Tests for air leakage are performed under laboratory conditions. In actual usage, results may vary
because of installation and/or environmental conditions. See Appendix A6.
1.7 For the purpose of this Standard, a firestop system refers to a specific
construction consisting of:
A Any device intended to close off an opening or penetration during a fire;
B Material(s) that fill an opening in a wall or floor assembly where penetration
is by cables, cable trays, conduits, ducts and pipes and any termination
devices, such as electrical outlet boxes along with their means of support
through the wall or floor opening;
C Material(s) and construction intended for use in linear openings between
adjacent fire resistive structures.
1.8 The testing of a joint firestop system placed into a perimeter joint located
between a fire rated floor and a non fire rated exterior wall is not intended to be tested using this
test method.
OEN:
ULC
Langue:
English
Code(s) de l'ICS:
13.220.10
Statut:
Annulée
Date de Publication:
2005-06-30
Numéro Standard:
CAN/ULC-S115-05