CSA 4.9-2000
1.1 Scope
1.1.1 This standard applies to newly produced gas-fired low-pressure steam and
hot water boilers with gas inlet pressures not exceeding ½ psi (3.45 kPa) and
having input ratings of less than 12,500,000 Btu per hour (3 663 389 W) (see
Part IV, Definitions), hereinafter referred to as boilers*, constructed
entirely of new unused parts and materials, for operation at or below the
following pressures and temperatures:
Steam heating boilers
15 psi (103.42 kPa) steam pressure
Hot water heating boilers
160 psi (1.10 MPa) water pressure
250°F (121°C) water temperature
Hot water supply boilers
160 psi (1.10 MPa) water pressure
250°F (121°C) water temperature
a. For use with natural gas;
b. For use with manufactured gas;
c. For use with mixed gas;
d. For use with liquefied petroleum gases; and
e. For use with LP gas-air mixtures,
The construction of boilers for use with the above-mentioned gases is covered
under Part I.
The performance of boilers for use with the above-mentioned gases is covered
under Part II.
1.1.2 This standard applies to indoor type boilers, of other than the direct
vent which are categorized according to vent pressure and temperature as either
Category I, Category II, Category III or Category IV (see part IV,
Definitions), and to outdoor type boilers.
1.1.3 This standard also applies to direct vent boilers (see Part IV,
Definitions). A direct vent boiler anticipated by this standard is essentially
a balanced flue appliance with the air intake and vent outlet in proximity.
Other designs shall be subjected to such additional tests as believed necessary
at the discretion of the testing agency.
1.1.4 This Standard covers the method of test to determine combustion
efficiency for indoor boilers with input rates of 300,000 Btu/h (87 917 W) or
greater and the thermal efficiency for both indoor and outdoor boilers. (See
Exhibit E, Items Unique to Canada, for minimum efficiencies of indoor boilers
with input rates under 300,000 (87917 W) for sale in Canada).
1.1.5 If a value for measurement as given in this standard is followed by an
equivalent value in other units, the first stated value is to be regarded as
the specification.
1.1.6 All references to pressure throughout this standard are to be considered
gauge pressure, unless otherwise specified.
1.1.7 Exhibit E, Items Unique to Canada, contains provisions unique to, and
required by, Canada.
- - -
* See Exhibit E (E2.1) for boilers covered in Canada which exceed the above
limits in gas inlet pressure and/or input ratings.
OEN:
CSA
Langue:
English
Code(s) de l'ICS:
27.060.30
Statut:
Annulée
Date de Publication:
2001-01-31
Numéro Standard:
CSA 4.9-2000