CSA 6.22-M97 (R2001)
1.1 SCOPe
1.1.1 This standard applies to line pressure regulators, (see Part V,
Definitions), constructed entirely of new, used parts and materials,
hereinafter referred to as regulator(s), either individual or in
combination with over pressure protection devices, hereinafter referred
to as device(s), intended for application in natural gas piping systems
between the service regulator and the gas appliance(s).
1.1.2 This standard applies to regulators classified in accordance with their
intended application with reference to inlet and outlet pressures as
follows.
Maximum Outlet Pressure
Rated
Inlet Pressure Class I Class Ii
-------------- ---------------- ----------------
2 psi (13.8 kPa) ½ psi (3.48 kPa) ---------
5 psi (34.5 kPa) ½ psi (3.48 kPa) 2 psi (13.8 kPa)
10 psi (68.9 kPa) ½ psi (3.48 kPa) 2 psi (13.8 kPa)
1.1.3 This standard applies to regulators and devices intended for use in one
or more of the following mounting classifications (see 1.12-a):
Upright-single position on a horizontal axis with respect to the inlet
connection, as specified by the manufacturer.
Horizontal-any position on a horizontal axis with respect to the inlet
connection.
Vertical-any position on a vertical axis with respect to the inlet
connection.
Limited Horizontal-any position from upright to 90 degrees (1.57 rad)
from upright on a horizontal axis with respect to the inlet connection.
Multipoise-any position on a horizontal, vertical or intermediate axis
with respect to the inlet connection.
The tests specified herein shall be conducted with the regulator
mounted in the manufacturer's specified upright position, unless
otherwise sepcified herein.
If the manufacturer specifies more than one mounting position, the
tests in 2.7 shall be conducted in each mounting position. The data
from these tests shall then be analyzed to determine the mounting
position which produces the minimum outlet pressure and the mounting
position which produces the maximum outlet pressure, based on results
observed for the minimum outlet pressure setting of the regulator.
a. The tests in 2.8 shall be conducted in the mounting position
which produces the minimum outlet pressure, as determined in
2.7.
b. The tests in 2.8 and 2.9 shall also be conducted in the
mounting position which produces the maximum outlet pressure,
as determined in 2.7.
1.1.4 The tests specified herein shall be conducted at a room temperature of
77 ± 10°F (25 ± 5.5°C). Regulators and vent limiters complying with
the provisions of this standard shall be considered as having an
operating temperature range of 32°F (0°C) to 125°F (51.5°C). At the
option of the manufacturer, a greater operating temperature range may
be specified, in which case additional tests as outlined in 2.4 and
2.10 shall be conducted.
1.1.5 If a value for measurement as given in this standard is followed by an
equivalent value in other units, the first stated value is to be
regarded as the specification.
1.1.6 All references to psi throughout this standard are to be considered
gage pressures unless otherwise specified.
PART Ii
PERFORMANCE - LINE PRESSURE REGULATIONs
2.1 GENERAl
2.1.1 Unless otherwise specified, tests for compliance with this standard
shall be conducted at 77 ± 10°F (25 ± 5.5°C), hereinafter referred to
as room temperature.
2.1.2 Separate overpressure protection devices shall be included in the test
setup, in accordance with the manufacturers instructions, for the tests
in 2.7, 2.8 and 2.10.
PART IIi
OEN:
CSA
Langue:
English
Code(s) de l'ICS:
91.140.40;
23.060.40
Statut:
Annulée
Date de Publication:
1998-03-30
Numéro Standard:
CSA 6.22-M97 (R2001)