CAN/CSA-B64.10-94
1. Scope
1.1
This Standard covers the selection, installation, maintenance, and field
testing of backflow prevention devices. Additional information on how backflow
due to back siphonage and back pressure occurs and on the selection and
application of specific devices is included in Appendices A, B, and C.
1.2
This Standard does not include requirements for materials, construction, and
performance tests of the backflow preventer. Such requirements for the
majority of the devices are covered in the CAN/CSA-B64 Series and CSA Standard
B125 (see Table 1).
1.3
Notes to the text do not include mandatory or alternative requirements. The
purpose of a note is to separate from the text explanatory or informative
material that is not properly a part of the Standard. Notes to figures and
tables are to be considered part of the figure or table and are written as
mandatory requirements. Legends to figures are to be considered mandatory
requirements.
1.4
This Standard is predominantly written in SI (metric) units; for conversion
tables, see Appendix D. However, because the test equipment currently
available was designed in yard-pound units, calibration must be in those same
units and therefore the requirements in the relevant Clauses (6.4.2.1, 6.5.1,
6.6.1, and 6.7.1) are also specified in yard-pound units.