C22.2 No. 65-93 (R1999)
1.1
This Standard applies to connectors for use with copper or aluminum conductors,
or both, for providing contacts between current-carrying parts such as
terminals, between lengths of wire and tap connectors, in accordance with the
Canadian Electrical Code, Part I, as follows:
(a) pressure wire connectors intended to hold one or more copper or
aluminum conductor(s);
(b) connectors intended for use in appliances and equipment that comply with
the requirements for such appliances and equipment;
(c) soldering connectors;
(d) splicing wire and cable connectors intended for use with No. 4 AWG and
larger; and
Note: A splicing wire and cable connector taking a range of conductor sizes
may include conductor sizes smaller than No. 4 AWG.
(e) neutral bars.
1.2
This Standard is intended for connectors suitable for use with conductors in
the size range shown in Table 1, and as follows:
(a) Aluminum
(i) 12 AWG and 10 AWG solid; and
(ii) 12 AWG to 2000 kcmil stranded, Class B (see ASTM Standard B8)
(b) Copper
(i) 30 AWG to 10 AWG solid or stranded; and
(ii) 8 AWG to 2000 kcmil stranded, Class B or C (see ASTM Standard
B8).
For further information about the conductors see ASTM Standards B8, B172, B173,
B174, B231M, B400, B496, and D471.
Note: Other sizes within the above ranges and other strandings may be
acceptable if they meet the performance requirements of this Standard.
1.3
This Standard does not apply to connectors intended for direct burial;
connectors for use at voltage levels in excess of 600 V (1000 V in a sign or
luminaire); manually applied (twist-on) connectors; built-in terminal
connectors on devices rated less than 30 A; and connectors intended for
outlet-box mounting or having provision for stress relief.
1.4
The values given in SI (metric) units are the standard. The values given in
parentheses are for information only.
OEN:
CSA
Langue:
English
Code(s) de l'ICS:
29.120.20
Statut:
Annulée
Date de Publication:
1993-05-30
Numéro Standard:
C22.2 No. 65-93 (R1999)