Pull Out commutateurs
Porté:
1 Scope
1.1
This covers construction, marking and test requirements for pullout switches of the detachable type, rated up to 600 V and 400A.
1.2
These requirements apply to non-enclosed and enclosed pullout switches of the detachable type.
1.3
These requirements apply to pullout switches rated 600 V or less, 400 A or less, with or without horsepower ratings, and with or without high-available fault current ratings.
1.4
These requirements apply to pullout switches mounted in an enclosure which may contain meter sockets or bonding assemblies or both.
1.5
These requirements do not apply to hinged pullout switches which are covered in C22.2 No. 4, Enclosed and Dead-Front Switches.
1.6
These requirements do not apply to enclosed pullout switches containing more than one independent switch which are covered in C22.2 No. 29, Panelboards.
1.7
Pullout switches shall not be used in the service box
Raison d’être du projet
Note : L’information ci-dessus a été recueillie et est diffusée par le Conseil canadien des normes (CCN) pour les besoins de son système de notification centralisé et transparent pour l’élaboration de nouvelles normes. Le système permet aux organismes d’élaboration de normes (OEN) accrédités par le CCN et aux membres du public d’être informés des nouveaux travaux d’élaboration de normes au Canada. Il donne aussi aux OEN accrédités la possibilité de repérer et de résoudre les cas de doubles emplois éventuels dans les normes et les travaux de normalisation.