Parafoudres - Type 1 - Connectés en permanence

Logo
CSA Group
Organisme d'élaboration de normes:
Programme de travail:
Numéro de référence:
C22.2 NO. 269.1-17
Catégorie de norme:
Norme nationale du Canada - Norme canadienne
Type d’activité d’élaboration de normes:
Confirmation
Code ICS:
29.120
Statut:
En cours d'élaboration
Date de début de la période de commentaires OEN:
Date de fin de la période de commentaires des OEN:
Affiché le:

Porté:

Champ d’application

1.1
This Standard applies to surge protective devices (SPDs) intended for: 

a) permanently connected applications designed for limiting surge voltages and discharging surge currents; 
b) use on 50/60 Hz circuits over 42 V and up to 750 V ac; 
c) installation between the secondary of the service transformer and the line side of the service equipment overcurrent protective device. These devices may also be installed on the load side of the main overcurrent protective device; 
d) installation where external overcurrent protection may not be present; and 
e) indoor or outdoor use in accordance with the Canadian Electrical Code, Part I. 

1.2
Type 1 SPDs intended for use in lightning protection systems are within the scope of this Standard. 

1.3
Equipment designed solely for other power disturbances such as notches, sags and noise is not within the scope of this document. 

1.4
SPDs discussed in this standard contain at least one voltage limiting or voltage switching component for diverting surge currents or dissipating surge energy, or both. Examples of such components are metal oxide varistors, silicon avalanche diodes, spark gaps and gas discharge tubes. Ferroresonators, motor- generators, uninterruptible power supplies, and filters containing only inductive or capacitive components are not considered SPDs in this standard. 

1.5
In this Standard, shall is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; should is used to express a recommendation or that which is advised but not required; and may is used to express an option or that which is permissible within the limits of the standard. 

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material. 

Notes to tables and figures are considered part of the table or figure and may be written as requirements. 

Annexes are designated normative (mandatory) or informative (nonmandatory) to define their application.

Raison d’être du projet

Raison d’être du projet
To review the Standard within the required 5 year period.

Note : L’information ci-dessus a été recueillie et est diffusée par le Conseil canadien des normes (CCN) pour les besoins de son système de notification centralisé et transparent pour l’élaboration de nouvelles normes. Le système permet aux organismes d’élaboration de normes (OEN) accrédités par le CCN et aux membres du public d’être informés des nouveaux travaux d’élaboration de normes au Canada. Il donne aussi aux OEN accrédités la possibilité de repérer et de résoudre les cas de doubles emplois éventuels dans les normes et les travaux de normalisation.

Les OEN sont eux-mêmes responsables du contenu et de l’exactitude de l’information présentée ici. Cette information n’existe que dans la langue dans laquelle elle a été fournie au CCN.