Exigences relatives aux performances des thermostats dédiés au chauffage électrique par pièce
Porté:
This Standard specifies performance requirements for thermostat models intended for line-voltage (120 to 240 V) switching of a controlled resistive heating load.
The models covered by this Standard are as follows:
a) wall-mounted line-voltage thermostats used with baseboards, panel convectors, fan-forced heaters or radiant floors;
b) built-in line-voltage thermostats (up to 1500 W) used in baseboards, panel convectors or fan-forced heaters; and
c) two-component thermostats.
This Standard's requirements apply only to local zone thermostats; they do not apply to central heating units under the control of a single thermostat and thermostats in portable heaters.
Thermostats not covered by this Standard
Thermostats used exclusively or built-in in the following units are excluded:
a) ceiling-mounted fan-forced heaters;
b) floor-mounted fan-forced;
c) kick space; and
d) fireplaces.
Raison d’être du projet
Note : L’information ci-dessus a été recueillie et est diffusée par le Conseil canadien des normes (CCN) pour les besoins de son système de notification centralisé et transparent pour l’élaboration de nouvelles normes. Le système permet aux organismes d’élaboration de normes (OEN) accrédités par le CCN et aux membres du public d’être informés des nouveaux travaux d’élaboration de normes au Canada. Il donne aussi aux OEN accrédités la possibilité de repérer et de résoudre les cas de doubles emplois éventuels dans les normes et les travaux de normalisation.