Commandes électriques automatiques - Partie 2-14: Règles particulières pour les actionneurs électriques

Logo
CSA Group
Organisme d'élaboration de normes:
Programme de travail:
Numéro de référence:
CAN/CSA-E60730-2-14
Catégorie de norme:
Norme nationale du Canada - Adoption d'une Norme internationale
Type d’activité d’élaboration de normes:
Nouvelle version
Statut:
En cours d'élaboration
Date de début de la période de commentaires OEN:
Date de fin de la période de commentaires des OEN:
Affiché le:

Porté:

Champ d’application

This clause of Part 1 is applicable except as follows:

1.1   Replacement:

 

This part 2-14 applies to electric actuators for use in, on, or in association with equipment for household and similar use. The equipment may use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof.

NOTE   Throughout this standard the word "equipment" means "appliance and equipment." EXAMPLE 1   Electric actuators for appliances within the scope of IEC 60335.

This International Standard is applicable to controls for building automation within the scope of ISO 16484.

 

This part 2-14 also applies to automatic electrical controls for equipment that may be used by the public, such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial applications.

 

EXAMPLE 2   Controls for commercial catering, heating and air-conditioning equipment.

 

This part 2-14 is also applicable to individual electric actuators utilized as part of a control system or controls, which are mechanically integral with multifunctional controls having non-electrical outputs.

 

EXAMPLE 3 Independently mounted water valves, controls in smart grid systems and controls for building automation systems within the scope of ISO 16484-2.

 

This part 2-14 does not apply to automatic electric actuators intended exclusively for industrial process applications unless explicitly mentioned in the relevant part 2 or the equipment standard.

 

•             This part 2-14 applies to the inherent safety, to  the  operating  values,  operating times and operating sequences where such are associated with equipment safety and to the testing of electric actuators used in or in association with equipment.

 

NOTE Requirements for specific operating values, operating times and operating sequences may be given in the standards for appliances and equipment.

 

This standard is also applicable to the functional safety of low complexity safety related systems and controls.

 

This part 2-14 does not apply to electric actuators which are mechanically integrated with valves covered by a separate part 2, e.g. IEC 60730-2-8.

 

This part 2-14 does not apply to electric motors, requirements for which are contained in IEC 60034.

 

•             Requirements for manual switches not integral with an electric actuator are contained in IEC 61058-1.

 

 

1.1.3   Replacement

This part 2-14 applies to a.c. or d.c. powered electric actuators with a rated voltage not exceeding 690 V a.c. or 600 V d.c.

1.1.4   Replacement

 

This part 2-14 does not take into account the response value of an automatic action of an electric actuator, if such a response value is dependent upon the method of mounting the electric actuator in the equipment. Where a response value is of significant purpose for the protection  of  the  user,  or  surroundings,  the  value  defined in the appropriate household equipment or as determined by the manufacturer shall apply

Raison d’être du projet

Raison d’être du projet
To maintain alignment with international requirements.

Note : L’information ci-dessus a été recueillie et est diffusée par le Conseil canadien des normes (CCN) pour les besoins de son système de notification centralisé et transparent pour l’élaboration de nouvelles normes. Le système permet aux organismes d’élaboration de normes (OEN) accrédités par le CCN et aux membres du public d’être informés des nouveaux travaux d’élaboration de normes au Canada. Il donne aussi aux OEN accrédités la possibilité de repérer et de résoudre les cas de doubles emplois éventuels dans les normes et les travaux de normalisation.

Les OEN sont eux-mêmes responsables du contenu et de l’exactitude de l’information présentée ici. Cette information n’existe que dans la langue dans laquelle elle a été fournie au CCN.