Performances des chargeurs de batterie rapides EV DC
Porté:
The project will focus on DCFC with 20kW to 350kW of rated power output. The draft standard will
include test methods to determine efficiency at representative temperatures (e.g. -30C, -7C, 20C and
40C) and different loading conditions (e.g., 25%, 50%, 75%, 100% load). It will include weighting factors
representing typical climate conditions in Canada (-30°C to 40°C) and criteria for reporting of weighted
system efficiency. It will establish minimum efficiency criteria and levels for DCFC in Canada. Testing
shall include measurement and reporting of total harmonic distortion (THD), power factor, and reactive
power in the various operating modes indicated above.
The C810 draft standard will include an informative annex including guidelines for sizing, selection
and control of auxiliary/ancillary equipment for supply voltage transformation; improved power factor
mitigation of harmful harmonics; and provisions for heating and cooling loads, to optimize system
energy use during standby and partial on mode operation of EVSE DCFC equipment.
Raison d’être du projet
Note : L’information ci-dessus a été recueillie et est diffusée par le Conseil canadien des normes (CCN) pour les besoins de son système de notification centralisé et transparent pour l’élaboration de nouvelles normes. Le système permet aux organismes d’élaboration de normes (OEN) accrédités par le CCN et aux membres du public d’être informés des nouveaux travaux d’élaboration de normes au Canada. Il donne aussi aux OEN accrédités la possibilité de repérer et de résoudre les cas de doubles emplois éventuels dans les normes et les travaux de normalisation.