Commutateurs instantanés à usage général

Numéro de référence:
C22.2 NO.111
Catégorie de norme:
Norme nationale du Canada - Adoption d'une Norme internationale
Sous-catégorie de norme
Type d’activité d’élaboration de normes:
Révision/Modification
Code ICS:
29.120.40
Statut:
En cours d'élaboration
Date de début de la période de commentaires OEN:
Date de fin de la période de commentaires des OEN:
Affiché le:

Porté:

Champ d’application

1.1

The requirements of this Standard apply to manually operated, general-use snap switches for connection to copper (Cu) or copper-clad conductors used in accordance with the National Electrical Code (NEC), ANSI/NFPA 70, or the Canadian Electrical Code (CE Code), Part I, and and intended to be permanently connected in accordance with the NEC and the CE Code, Part I. In Canada, requirements for switches for connection to aluminum (Al) conductors used in accordance with the CE Code, Part I, and intended for connection to wiring systems recognized by the CE Code, Part I, are covered in Annex B.


1.2

This Standard applies to ac/dc rated switches for which the load ratings do not exceed 60 A at 250 V or less, 30 A at 251 V – 600 V, and 2 hp at 125 V – 600 V or less. This Standard also covers ac-only rated switches for which the load ratings do not exceed 30 A at 347 VAC or less.


1.3

This Standard applies to switches constructed to be installed readily in a flush device box or on an outlet-box cover and intended for connection to branch-circuit wiring.


1.4

This Standard applies to pendant and through-cord switches intended for field installation on flexible cord and
provided with one ″on″ and one ″off″ position.


1.5

This Standard applies to switches intended for surface mounting and provided with a separable base and cover for connection to exposed wiring consisting of nonmetallic sheathed cable or open wiring on insulators (knob and tube).


1.6

This Standard applies to self-contained switches intended for flush mounting without a separate outlet box and for connection to branch-circuit wiring consisting of one or more non-metallic sheathed cables containing copper conductors.


1.7

This Standard applies to ac/dc fixture switches intended to be installed in fixtures to control incandescent lighting or fans for connection to branch-circuit wiring.


1.8

This Standard also applies to single-pole, momentary-contact door switches constructed to be installed readily in a special-purpose device box or on an outlet-box cover for connection to branch-circuit wiring.

1.9

This Standard does not apply to:


a) Clock operated switches specified in the Standard for Clock-Operated Switches, UL 917, and CSA Standard
C22.2 No. 177;


b) Dimmer switches specified in the Standard for Solid-State Dimming Controls, UL 1472, and CSA Standard
C22.2 No. 184.1;

c) Industrial control equipment specified in the Standard for Industrial Control Equipment, UL 508, and CSA
Standard C22.2 No. 14;


d) Solid-state, single-phase motor speed controls specified in the Standard for Solid-State Fan Speed Controls, UL 1917, and CSA Standard C22.2 No. 156;


e) Special-use and ac-only fixture switches specified in the Standard for Switches for Appliances – Part 1:
General Requirements, UL 61058-1, and CSA Standard C22.2 No. 55; and f) Switches for use in hazardous locations specified in the Standard for Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations, UL 1203, and CSA Standard C22.2 No. 159.


1.10

For switches intended for connection to branch-circuit wiring containing aluminum conductors, refer to the Standard for Receptacles and Switches Intended for Use with Aluminum Wire, UL 1567, or to Annex B. In Mexico, this Clause is not applicable. The use of aluminum conductors from 0.824 mm2 (18 AWG) to 8.37 mm2 (8 AWG) is prohibited.

Raison d’être du projet

Raison d’être du projet
To update the current standard due to technical updates within the North American Region. This proposed Amendment is being developed at the request of CANENA Technical Harmonization Committee. The amendment will include an option for Field replaceable actuators and further requirements and clarifications for class 2 connectors used with general use switches.

Note : L’information ci-dessus a été recueillie et est diffusée par le Conseil canadien des normes (CCN) pour les besoins de son système de notification centralisé et transparent pour l’élaboration de nouvelles normes. Le système permet aux organismes d’élaboration de normes (OEN) accrédités par le CCN et aux membres du public d’être informés des nouveaux travaux d’élaboration de normes au Canada. Il donne aussi aux OEN accrédités la possibilité de repérer et de résoudre les cas de doubles emplois éventuels dans les normes et les travaux de normalisation.