Câble à isolant minéral
Porté:
Scope
- This standard applies to mineral-insulated cables with copper, nickel/nickel-alloy-clad-copper, steel-clad copper, or nickel conductors, enclosed in a copper or stainless steel sheath.
- The constructions covered by this standard are intended for use in power, instrumentation, control, and fire alarm systems in accordance with the Canadian Electrical Code, Part 1.
- The contructions covered by this standard are recognized for use where normal conditions are such that no part of the cable is subjected to a temperature in excess of 250°C. When provided with an overall thermoplastic or thermoset protective covering, the use is restricted to 90°C.
- The contructions covered by this standard are
a) Type MI mineral-insulated, copper sheathed cable recognized for use on systems having a nominal voltage of 600 V or less;
b) Type SSMI mineral-insulated, stainless steel-sheathed cable recognized for use on systems having a nominal voltage of 600 V or less;
c) Type LWMI mineral-insulated, copper-sheathed cable recognized for use on systems having a nominal voltage of 600 V or less; and
d) Type SSLWMI mineral-insulated, stainless steel-sheathed cable recognized for use on systems having a nominal voltage of 600 V or less.
1.5 Optional requirements are provided for
a) twisted pair configurations;
b) copper or stainless steel shields
c) overall thermoplastic or thermoset protective coverings
d) flame test classifications; and
e) fire rating
f) fire alarm and signal cable.
1.6 In CSA Standards, ”shall” is used to express a requirement, i.e. a provision that the user is obligated to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; “may” is used to express an option of that which is permissible within the limits of the standard. Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the test explanatory or informative material. Notes to tables and figures are considered part of the table or figure and may be written as requirements. Legends to equations and figures are considered requirements.
Note : L’information ci-dessus a été recueillie et est diffusée par le Conseil canadien des normes (CCN) pour les besoins de son système de notification centralisé et transparent pour l’élaboration de nouvelles normes. Le système permet aux organismes d’élaboration de normes (OEN) accrédités par le CCN et aux membres du public d’être informés des nouveaux travaux d’élaboration de normes au Canada. Il donne aussi aux OEN accrédités la possibilité de repérer et de résoudre les cas de doubles emplois éventuels dans les normes et les travaux de normalisation.